o PPM AS / PSS AS Capsule Microphone Short
Text messages display at touch screen on front panel of IDA8C:
"Remote Fault"
"PSS Port:1 ID:1, Microphone Fault", where Port N is the N
th
PDC port for peripheral
connection, ID is the unique number for each peripheral device on the PDC port.
Text message display at window [Machine Fault Record] of Ateis Studio:
o PPM AS / PSS Speaker Error
Text messages display at touch screen on front panel of IDA8C:
"Remote Fault"
"PSS Port:1 ID:1, Speaker Fault", where Port N is the N
th
PDC port for peripheral
connection, ID is the unique number for each peripheral device on the PDC port.
Text message display at window [Machine Fault Record] of Ateis Studio:
Buzzer sound output to monitoring speaker on front panel of IDA8C.
Fault Handling
Replace the error peripheral device by a good one, and contact service to repair bad one.
4.1.6.3 Procedure of Monitoring Setup
The monitoring setup must be done when hardware setup is appropriate, it means IDA8C/S, amplifiers,
speakers, wiring should be prepared and connected before monitoring setup, because IDA8C/S will get
values of hardware initial state for further reference, when system is running and reference values are
appropriate achieved, IDA8C/S continuity measure internal status and compare with referenced values to
determine if there are something wrong of zone/amplifiers or not.
1. Setup hardware equipment, including IDA8C/S, normal amplifier, backup amplifier, speakers, wiring
between devices,
2. Make a configuration using Ateis Studio.