Maximum Output Level = 10 dBu.
Output Impedance = 300 Ohm.
THD @ 1kHz at output < 0.02.
Bandwidth @ -3dB at output = 20Hz ~ 20kHz.
Noise @ 22Hz ~ 22kHz = -85dBu.
Maximum Input Level = 16 dBu.
Input Impedance = 11k Ohm.
THD @ 1kHz at input < 0.02
Bandwidth @ -3dB at input < 20Hz ~ 22kHz.
RS232 voltages = -6.5/+6.5
Evacuation Inputs(Contact Mode)
Bias voltage:
Item
Minimum
Maximum
Unit
Voltage
-
5
VDC
Monitoring resistor = 4.7k Ohm.
Evacuation Inputs(Voltage Mode)
On Voltage:
Item
Minimum
Maximum
Unit
Voltage
18
72
VDC
Contact Outputs + EVAC, Fault State Outputs
Item
Minimum
Maximum
Unit
Voltage
-
100
VDC
Current
-
0.5
ADC
Working Temperature.
C ~ 40°C
4.1.2.5 Peripherals
Following table is the peripherals supported by IDA8SAB:
Device
Connection
Max. Num
Function
Fireman MIC
Fireman MIC
Input
1
Paging where operator is close to IDA8C.
PPM AS
PDC
31/PDC
Remote console for with paging ability.
PSS AS
PDC
1/PDC
Remote console for Paging, Event Triggering(Element Control,
Master/Sub Preset Control).
URC AS
PDC
1/PDC
Remote console for Master/Sub Preset Controlling, Element
Controlling.
URGP
PDC
1/PDC
Evacuation Input extension.